vaillant vuw int 180/1 XE, THERMOTOP combi central heating and boiler fault fix: FAULT: No hot water from the tap in the bathroom. PROBLEM: faulty micro switch. FIX: Disconnect power mains!!! remove the switch, check the conductivity with a multimeter. if the switch is faulty remove the green seal and drip some alcohol into the switch. Check the conductivity again. Let it dry upside down in a hot dry place. Buy a new one if it's still bad. Put it back, reconnect mains but keep an eye on the gas flame that might turn on without the switch is being pressed (if it is so the switch is not dry inside). thanks for watching ( atosmaximus (at) gmail.com :-)

  1. hwrxYiApZkgqVQen
    hwrxYiApZkgqVQen
    yPxQpo2jKkUDKxLd
    3TGNxMdukC6qjquu
    • PROBLEM: faulty micro switch. FIX: Disconnect power mains!!! remove the switch, check the conductivity with a multimeter.

  2. A2TGZPkeCoCaxJsU
    A2TGZPkeCoCaxJsU
    PiJ2asqwXgDxdOqF
    DgTsme5HADNbwOKI
    • FIX: Disconnect power mains!!! remove the switch, check the conductivity with a multimeter. if the switch is faulty remove the green seal and drip some contact cleaner (alcohol) into the switch. Check the conductivity again. Let it dry upside down in a hot dry place.

  3. EgknkDKRFIICSSAY
    EgknkDKRFIICSSAY
    h4Alc6g2AmvAEy4M
    • check the conductivity with a multimeter. if the switch is faulty remove the green seal and drip some alcohol into the switch. Check the conductivity again. Let it dry upside down in a hot dry place. Buy a new one if it's still bad.

  4. GiQ34qvImrjUuNXp
    • Put it back, reconnect mains but keep an eye on the gas flame that might turn on without the switch is being pressed (if it is so the switch is not dry inside). Say thanks to me ( atosmaximus (at) gmail.com :-)

Abschluss

To reassemble your device, follow these instructions in reverse order.